A study on the Insulation Condition Evaluation and Insulation Reinforced Method of Large Motors

대형모타 절연상태 판정기준 및 절연보강 방안 연구

  • Published : 2000.07.17

Abstract

This is the first report of a series of field test result of large high voltage generator & motors. Major specimens were 6.6/13.2kV class hydroric power & pump motor that was installed and operated for public water service by KOWACO(KOrea WAter resources COperation). The capacity of specimen gene rater & motors were in range of several hundred kVA$\sim$50MVA. Until now, we get the 100 field test result by testing technique discribed in IEEE standards and Discharge map technique from Japanse manufactures. The test result was varied very wide range, and there was a tendency according to insulation material and manufacture.

본 논문은 고압 전력기기인 대형모타에 대해 현장에서 정밀 진단한 것으로 주로 6.6/3.3kV급을 대상으로 하였으며, 수백 kW $\sim$ 5MW까지의 용량을 지니고 있는 것으로 현재 수자원공사 각 현장에서 설치 운용되고 있는 설비이다. 진단결과 간이 제조업체, 사용재료 등에 의한 절연간이 다양하게 그리고 넓은 범위로 나타났으며, 판정기법은 IE료El) 기준과 일본 제조업체에서 개발한 Discharge-map를 이용하였으며 '99년까지 100여 개소에 대하여 진단을 실시하였다.