시변 저항을 이용한 배전 계통의 고저항 사고 모델링

Modeling of a High Impedance Fault in a Distribution System Using Time-Varying Resistance

  • 발행 : 1999.11.20

초록

A more reliable relaying algorithm for detecting a high impedance fault (HIF) requires fault currents at the relaying point containing information of various HIF characteristics as well as load conditions. As HIF characteristics, there are buildup, shoulder, nonlinearity and asymmetry. This paper presents a modeling method of a HIF in a distribution system using EMTP. In order to represent HIF characteristics, the proposed method uses two time-varying resistances. The first TVR models nonlinearity and asymmetry using voltage as the input. The second TVR models buildup and shoulder using time information as the input. The proposed method is implemented in EMTP.

키워드