GIS내 파티클의 상태에 따른 전기적 방전 신호 분석

Analysis of Electrical discharge signal according to particle state in GIS

  • 발행 : 1999.11.20

초록

The breakdown was caused by particle in GIS and various methode was suggested to find particle in GIS. In this paper, four states of particle was imitated which are particle on electrode, particle on enclosure, particle on spacer and crossing particle. The discharge voltage of each states was classified by four voltages which are initial, development, later and close discharge voltage. $\Phi$-Q-N pattern was analyzed according to the states and to the discharge voltages. In the result, the electrical discharge pattern according to the particle states may be distinguished.

키워드