퍼지 위험도 평가 모델을 이용한 배전계통의 순간전압강하 영향 평가
Assessing the Effect of Voltage Sag in Distribution System Using a Fuzzy Risk Assessment Model
- 윤상윤 (숭실대학교 전기공학과) ;
- 오정환 (숭실대학교 전기공학과) ;
- 한병덕 (숭실대학교 전기공학과) ;
-
김재철
(숭실대학교 전기공학과) ;
- 박중신 (한국전력공사) ;
- 임동균 (한국전기안전공사)
- Yun, Sang-Yun (Dept. of E.E. in Soongsil Univ.) ;
- Oh, Jung-Hwan (Dept. of E.E. in Soongsil Univ.) ;
- Han, Byung-Duk (Dept. of E.E. in Soongsil Univ.) ;
-
Kim, Jae-Chul
(Dept. of E.E. in Soongsil Univ.) ;
- Park, Joong-Shin (KEPCO) ;
- Lim, Dong-Gyun (KESCO)
- 발행 : 1999.07.19
초록
In this paper, we propose the method for assessing the effect of voltage sag in power distribution system using fuzzy risk assessment model. The proposed method is based on SCBEMA curve that expresses the representative susceptibility curve by voltage sag for each customer type. These corves are made using the CBEMA curves obtained from the experiment for the customers'sensitive equipment. In order to transform SCBEMA curves to the probability damage by voltage sag, the fuzzy risk assessment model is used in this paper. Case studies were performed to analyze the effect of voltage sag by varying parameters. The Monte Carlo simulation method and the historical reliability data in KEPCO are used for case studies.