A Study on the Dielectric Properties of Lightening Arrester used for Distribution Line

배전용 피뢰기의 유전특성에 관한 연구

  • 김찬영 (한국전력공사 전력연구원) ;
  • 김주용 (한국전력공사 전력연구원) ;
  • 송일근 (한국전력공사 전력연구원) ;
  • 이병성 (한국전력공사 전력연구원) ;
  • 한용희 (한국전력공사 전력연구원)
  • Published : 1999.07.19

Abstract

This paper provides the results of dielectric properties for aged or controlled lightening arresters. The aged lightening arresters were used for five years in distribution line. The leakage current of lightening arresters and elements was measured to confirm whether the lightening arrester was deteriorated or not. The microstructure was also investigated to determine the size of grain and grain boundary. The dielectric properties of aged lightening arresters were compared to those of controlled lightening arresters. The dielectric constant and the tan${\delta}$ of aged lightening arrester were larger than those of controlled one, resulting from accelerated aging due to the thin grain boundary.

Keywords