Assessment of Insulation Condition in High Voltage Motor Stator Windings

고압전동기 고정자 권선의 절연상태 평가

  • Published : 1999.07.19

Abstract

This paper describes to access the insulation deterioration condition of the stator windings in six high voltage motors. Nondestructive tests have been carried out on stand-still motors. These tests include ac current increase rate($\Delta$I), delta tan delta(${\Delta}tan{\delta}$), and maximum partial discharge(PD). AC current and $tan{\delta}$ were measured by Schering bridge. The measurement of PD patterns were conducted using digital partial discharge detector. PD patterns were observed treeing and internal discharges in Motor 1 and 2. The stator windings of two motors were found to be in a poor condition and their were recommended to rewind. The stator. windings of four motors were judged to be in serviceable condition.