Failure Analysis of Underground Transmission Cable Systems

국내 지중 케이블 고장현황 분석

  • Published : 1999.07.19

Abstract

In order to analyze failure rates of underground transmission power cable systems in Korea, the survey has been performed for the failure cases of cables, joints, and terminations in CV, OF and POF cable systems which occurred from 1983 to 1998. During 16 years, the failure cases due to trips of the systems were 47 among the total 108 cases, These 47 cases could be divided into internal reasons(manufacture/installation, corrosion and degradation) of 16 cases and external reasons (external mechanical damages, lightning, fire. etc.) of 31 cases. For the 154 kV cable systems during 12 years from 1987 to 1998, total failure rate was 0.0057 [case/100C-km/year] and internal reason failure rate was 0.0020 [case/100C-km/Year], which is similar to those of foreign countries. Also, the many cases of internal reason failures occurred in the early stage after the operations due to incorrect installations. This implies that the installation process is very important and some diagnostic tests such as PD measurement are needed besides after laying test.

Keywords