Effects of Maximum Probe Spacing of Wenner Method on Substation Grounding

변전소 접지설계를 위한 대지저항율 측정시 전극간격이 해석결과에 미치는 영향

  • Published : 1999.07.19

Abstract

Estimating equivalent soil model which represents an actual soil structure and its electrical characteristics, is extremely improtant for good substation grounding system design and analysis. Since the equivalent soil model is deduced based on the measured apparent soil resistivity - generally obtained from Wenner's 4-point method, reasonable and accurate measuring technique and procedure guarantee good grounding system design and analysis. The paper aims to show the importance of reasonable enough probe spacing by presenting the influence of soil modelling to estimation and measurement of grounding resistance of substation grounding grid.

Keywords