접촉전압 저감을 위한 변전소 접지망 설계
Design of Substation Grounding Grid for Reduction of Touch Voltage
- Choi, J.K. (KEPRI) ;
- Kee, H.C. (KEPRI) ;
- Jung, G.J. (KEPRI) ;
- Kim, B.J. (KEPCO)
- 발행 : 1999.07.19
초록
The purpose of substation grounding system is to provide reference potential with power system and protect field workers from electrical shock resulted from unsymetrical power system faults. For this purpose, grounding grid should be designed to maintain max, touch voltage under safety criteria in fault conditions. It is difficult, however, to design a safe grounding grid at very resistive or narrow area. This paper describes an example of substation grounding grid design procedures in such areas with very severe design conditions. By using grounding conductors, which is located close to earth surface, earth surface potential could be controlled effectively, so that maximum touch voltages is to be maintained under safety criteria.