Performance Test of 200-MW Pulse Transformer for 80-MW Klystron Load

80-MW 클라이스트론 부하용 200-MW 펄스 트랜스포머의 성능시험

  • Jang, S.D. (Pohang Accelerator Laboratory, Postech) ;
  • Oh, J.S. (Pohang Accelerator Laboratory, Postech) ;
  • Son, Y.G. (Pohang Accelerator Laboratory, Postech) ;
  • Cho, M.H. (Pohang Accelerator Laboratory, Postech)
  • 장성덕 (포항공과대학교 가속기연구소) ;
  • 오종석 (포항공과대학교 가속기연구소) ;
  • 손윤규 (포항공과대학교 가속기연구소) ;
  • 조무현 (포항공과대학교 가속기연구소)
  • Published : 1999.07.19

Abstract

A pulse transformer producing pulses with the peak power of 200-MW (400 kV 500 A at load side with $4.4{\mu}s$ flat-top) is required to drive the 80-MW pulsed klystron in the PLS linac. We have designed and manufactured the high power pulse transformer with 1 : 17 turn ratio. Its primary functions are to match the impedance of klystron tube to the modulators, and to provide step-up of the voltage. To obtain a fast rise time of the pulse voltage. Low leakage inductance and low distributed capacitance design is very important. In this paper, we discuss the equivalent circuit analysis of the pulse transformer, and present the full power performance test results of pulse transformer.