Characteristics of Dissipation Factor in High Voltage Motor Stator Insulations

고압전동기 고정자 권선 절연재료에서 유전정접 특성

  • Published : 1999.07.19

Abstract

The insulation condition of stator windings was measured by dissipation factor($tan{\delta}$) test in the six high voltage motors(rated 6.6kV) which had been in service for two years. The ${\Delta}tan{\delta}$ of motor D and E was higher than that of the rest motors. The specimens were drawn out from stator windings of the high voltage motor and their were analyzed using scanning electron microscope (SEM). SEM result shows that large voids are present in the interface both turn insulation and groundwall insulation.