Assessment of Insulation Condition in Large Turbine Generator Stator Windings

대용량 터빈발전기 고정자 권선의 절연상태 평가

  • Published : 1999.07.19

Abstract

This paper describes to access the insulation deterioration condition of the stator windings in three large turbine generators. Nondestructive tests have been carried out on stand-still generators which have been in service for 2 to 30 years. In most cases these tests include ac current increase rate($\Delta$I), delta tan delta( ${\Delta}tan{\delta}$), and maximum partial discharge(Qm). Gen. 2 show that the $tan{\delta}$ is higher than other two generators in the $tan{\delta}$-voltage curve. Partial discharge(PD) patterns were observed internal, corona and treeing discharges in large turbine generators. The PD tests were confirmed the correlation between discharge patterns and the kinds of defects.

Keywords