A analysis result on the lightning outage and the lightning shield at 154 kV substation

154 kV 변전설비의 낙뢰사고 원인해석과 차폐검토

  • Published : 1999.07.19

Abstract

This paper describes the analysis results for the protection of lightning surge at 154 kV substation. We found that the surge arrester is needed at the inlet structure. The maximum overvoltage is 975 kV at the circuit breaker without the surge arrester at the inlet structure. This value can be lower than 600 kV by installing the surge arrestor at the inlet structure. In addition to the incoming surge from transmission line, the shield wire should be considered to prevent the shielding failure by the direct lightning stroke.