Proceedings of the KIEE Conference (대한전기학회:학술대회논문집)
- 1999.07e
- /
- Pages.2076-2079
- /
- 1999
A analysis result on the PT ferroresonance at 154 kV GIS substation
154 kV GIS의 PT 철공진 소손사례와 원인규명
Abstract
This paper describes the analysis results on the PT ferroresonance at 154 kV GIS (gas Insulated substation by EMTP (Electro-magnetic Transient Program). We had simulated the PT ferroresonance between a potential transformer(PT) and an open circuit breaker's grading capacitance. The ferroresonance leads to very large power frequency overvoltages on PT bus and subsequent insulation failure. The large power can be supplied to the PT by the high voltage on the opened circuit due to the grading capacitance and equivalent capacitance of the buses during the ferroresonance. The damping circuit connected on the secondary winding were considered in the model. The actual countermeasure include a saturable inductor and a resistor series-mounted, but the 2 ohms of damping resistance was used in the computational model.
Keywords