A analysis result on the application of HSGS to the 765 kV transmission line according to it's length

765 kV 계통의 송전선로 거리에 따른 HSGS 적용에 관한 연구

  • Published : 1999.07.19

Abstract

The extended 765 kV system may have severe electrical transients according to the interconnection of transmission lines and have long transmission line over 250 km. So we need to analyze the transient phenomena to confirm the insulation coordination which is designed for 765 kV project step I. In particular, this paper shows the analysis results of secondary arc extinction by HSGS (high speed ground switch) application. The EMTP/MODELS were used to simulation study of secondary arc phenomena. We had confirmed the TRV(transient recovery voltage) and rated current of HSGS which will be used in the KEPCO 765 kV system.

Keywords