A Study on the capacity of shunt type active power filter with a thyristor converter load
싸이리스터 컨버터부하를 가지는 병렬형 능동전력필터 용량에 관한 연구
- Park, No-Joong (Dept. of Electrical Engineering, Kwangwoon univ.) ;
- Joeng, Seung-Gi (Dept. of Electrical Engineering, Kwangwoon univ.)
- Published : 1999.07.19
Abstract
The main drawback of parallel type active power filters (APFs) is the large capacity required for harmonic compensation. This paper evaluates the APF capacity requirement for harmonic/reactive power compensation for thyristor converter load. Theoretically achievable maximum power factor under partial load is evaluated. it is shown that the APF capacity can be considerably reduced by deliberately limiting the peak current, while maintaining the filtering performance with an acceptable total harmonic current level. the minimum capacity requirement of APF with current limiting is evaluated as a function of the firing angle of thyristor converter and short circuit ratio(SCR).