Anti-Contamination Capability of Gas Insulated Switch for Distribution Line

배전용 가스개폐기의 내 오손 성능향상 대책

  • Published : 1998.11.28

Abstract

This paper provides the results of performance investigation of gas insulated switches(G/S) for distribution power system. In order to investigate anti-contamination capability of G/S we carried out electrical tests and material analysis on the body of G/S and it's accessories. Through this experiment we found out the lead cable of G/S had not anti-contamination capability and G/S had insufficient interval between each phase. In order to improve the performance of G/S for heavy contamination area it is indispensable to replace the lead cable to the new cable which has anti-contamination ability.

Keywords