격납건물 텐던갤러리 벽체의 온도응력에 대한 연구

A Study on Thermal Stress in T/G Wall of Containment Building

  • 김진근 (한국과학기술원 토목공학과) ;
  • 양은익 (한국해양연구소) ;
  • 박영진 (한국과학기술원 토목공학과) ;
  • 송영철 (한국전력공사 전력연구원 책임연구원) ;
  • 방기성 (한국전력공사 전력연구원)
  • 발행 : 1998.04.01

초록

In this study, the change of concrete temperature, strain and thermal stress were measured by using the embedded type concrete gauges in tendon gallery wall of containment building. A finite element analysis was performed to clarify the thermal behavior of concrete. The analytic and test results were investigated to improve the validity of analytic method. According to the test results, concrete temperature, strain and thermal stress were strongly affected by measuring point and environment condition of member. And the thermal stress was developed in the member which was not demoulded at early ages. This is caused by the change of internal temperature and restrained condition. A finite element effectively interpreted the test results by estimating the concrete properties and the site condition.

키워드