Reduction of EMI Generated by a PWM Inverter-Fed AC Motor Dirve System

  • Published : 1998.10.01

Abstract

This paper deal with problems of leakage current, shaft voltage, bearing current, and EMI, in valiable-speed AC drives. The originating mechanism is illustrated with a high-frequency equivalent circuit. Reduction methods are classified in to six categories based on the equivalent circuit. Some experimental results show that a common-mode transformer (CMT) and a common-noise canceler (ACC) can solve the problems, which have been proposed the authors.

Keywords