Fuzzy-PI Cascade Control of Drum Level of Boiler in Thermal Power Plan

화력 발전소 드럼수위의 퍼지-PI 캐스케이드 제어

  • 변승현 (전력연구원 시스템통신연구소) ;
  • 조지용 (전력연구원 시스템통신연구소) ;
  • 김동욱 (전력연구원 시스템통신연구소)
  • Published : 1998.07.20

Abstract

The drum level control is initiated by 1-element manual control, and then the control mode is changed to 1-element automatic control mode. Finally, the drum level control is changed to 3-element automatic control mode by the logic based on pre-defined threshold of main steam flow. In terms of plant automation, the automatic 1-element control mode is required from the start-up of boiler. In this paper, the fuzzy controller is adopted for automatic 1-element control of drum level from start-up. It is suggested that the fuzzy controller is used in 1-element control, and the fuzzy-PI cascade controller is used in 3-element control. Finally, the validity of suggested control scheme is shown via simulation.

Keywords