Field test Results for PSS Parameter Tuning in Seo-Incheon Power Plant

서인천 복합화력 발전소의 PSS 파라메터 Tuning

  • 신정훈 (한국전력공사 전력연구원) ;
  • 김태균 (한국전력공사 전력연구원)
  • Published : 1998.07.20

Abstract

Static excitation systems with high gain and fast response times greatly aid transient stability. but at the same time tend to reduce small signal stability. The objective of the power system stabilizer(PSS) control is to provide a positive contribution to damping of the generator rotor angle swings, which are in a broad range of frequencies in the power system. Therefore, this paper shows the field test results for the GE's EX2000 PSS tuning on units at Seo-Incheon power plant. The test is to verify that the PSS response meets GE's design, criteria. The responses of generator terminal voltage, active power, field voltage and current were analyzed and PSS gain was tuned by 10 finally.