This paper describes the dissipation factor measuring device for insulating oil in operating pole transformer by DSP(digital signal processor). After applying voltage to the sensor which is installed in a transformer, acquire source voltage and current of sensor using FFT techniques, then we could evaluate the dissipation factor of insulating oil. To improve measuring accuracy and processing speed, we use TMS320C31 DSP, FFT and data analysis techniques. Also we suggest deterioration criterion of insulating oil and compared the developed diagnosis device with schering bridge on deteriorated insulating oil. The result of this paper show that the developed measuring device can be used as diagnosis device for the pole transformers.