배전선로 보호협조 개선을 위한 리클로져 TC커브 변경

Changes of Recloser's TC Curve for the Improvement of Distribution Line Protection Coordination

  • 발행 : 1998.07.20

초록

The TC curve of recloser which used in KEPCO's distribution line is a little different in a pattern with the TC curve of sub-station OCR. So it sometimes fails in protection coordination. And the recloser sometimes does mis-open/close owing to the inrush current of CB reclosing when a fault occurred on the source-side of the recloser. The mis-open/close is another trouble maker. This Paper Present a new delay TC curve of recloser which has the same pattern with the TC curve of OCR, and a new instantaneous TC curve of recloser which doesn't mal-function to the inrush current. In addition, this paper present another two TC curves for the serial positioning of 2 reclosers. So we accomplished the simple protection coordination of OCR-recloser-fuse.

키워드