Effect of Phase Arrangement on Magnetic Field of Overhead Transmission Lines

송전선로의 상배열이 자계 크기에 미치는 영향

  • 김상범 (한국전력공사 전력연구원) ;
  • 이동일 (한국전력공사 전력연구원) ;
  • 신구용 (한국전력공사 전력연구원) ;
  • 김점부 (한국전력공사 전력연구원)
  • Published : 1998.07.20

Abstract

The purpose of this study is to obtain optimum arrangement of phase conductors in minimizing magnetic field from overhead transmission lines. Data of the transmission lines rated 345 kV of the KEPCO(Korea Electric Power Company)'s system were used. For a three phase-double circuit transmission line, low-reactance arrangement is optimum in minimizing magnetic fields. For a three phase-four circuit, optimum phase arrangement is a-b-c-b-a-c(lower two circuits, clockwise)/b-c-a-c-a-b(upper two circuits, clockwise).