Optimal Protecting the Static Excitation Equipment and Rotor Windings of Synchronous Machines Against Overvoltage
대용량 발전기 정지형 여자시스템 계자회로에 발생되는 최적 과전압 억제 회로
Abstract
In the case of synchronous machines, certain power system disturbances cause the induced rotor current to assume negative values when no static converter is present. A converter, however. prevents negative current from flowing, so that overvoltages occur. The overvoltages can be effectively limited as crowbar circuit using GTO. This newly proposed crowbar circuit with current limiting resistor absorbs energy when overvoltage comes from power system repeatedly and is verified through experiment.
Keywords