아트리움 공간에 있어서 화재에 의한 연기 유동에 관한 수치해석적 연구

  • Published : 1997.11.01

Abstract

The smoke filling process for the atrium space containing a fire source is simulated using two types of deterministic fire modus: Zone model and Field model. The zone mode used is the CFAST(version 1.6) mode developed at the Building and Fire Research laboratories, NIST in the USA. The lied model is a self-developed fire field model based on Computational Fluid Dynamics(CFD) theories. This article is focused on finding out the smoke movement and temperature distribution in atrium space which is cubic in shape. A computational procedure for predicting velocity and temperature distribution in fro-induced flow is based on the solution, in finite volume method and non-staggered grid system, of 3-dimensional equations for the conservation of mass, momentum, energy, species and so forth. The fire model i. e. Zone model and Field model predicted similar results for Ire clear height and the smoke layer temperature.

아트리움 공간에서 화재 발생시 연기 유동에 대하여 두 가지 형태의 화재 모델인 zone 모델과 field 모델을 이용하여 시뮬레이션 했다. 사용된 zone model은 NIST에서 개발된 CFAST(version 1.6) 모델이며 field 모델은 전산유체역학 이론을 바탕으로 자체 개발된 화재 모델이다. 본 연구는 정육면체 모양의 아트리움 공간에서 연기 유동과 온도 분포에 대하여 해석하고자 한다. 화재로 인해 야기된 유동에 대하여 속도장과 은도장을 예측하기 위한 계산 과정은 유한체적법 및 비엇갈림격자계를 이용하여 질량, 운동량, 에너지 및 성분 보존 방정식등에 대한 3차원 비정상상태 지배방정식을 사용했다. 수치해석 결과 zone 모델과 field 모델의 화재 모델에 의해 예측된 연기 층 평균 경계놀이와 상부 더운 연기 층의 평균 온도에 대하여 거의 유사한 결과를 얻었다.