방호 구조물에 강섬유보강 콘크리트의 적용
Application of SFRC on the Protection Structure(SPIN TESTER)
초록
The Spin Tester(High Speed Balancing and Overspeed Test Facility), which is designed for the quality control of turbine, generator, and rotors was supposed to be constructed with the use of Steel Fiber Reinforced Concrete(SERC) for reducing the risk of accident while operation. However, it was very existence of fiber concrete due to there are two major concern in the SFRC work: one is existence of fiber ball due to inhomogeneous mixing, the other is the segregation of the concrete materials. To avoid these possible problems, the S/a was controlled about 55% to reduce the segregation and the high range AE water reducing agent was used to maintain the slump over the value of 18cm. With these careful consideratons, the SFRC work was done successfully by only using regular equipments like pump car and vibrator.