The flexural of Ultra High Strength Reinforced Concrete Beams

초고강고 RC보의 휨거동

  • 정철규 (정회원, 한양대 대학원) ;
  • 조인철 (정회원, 한양대 대학원) ;
  • 안종문 (정회원, 한양대 대학원) ;
  • 이광수 (정회원, 여주전문대 건축과 조교수 공학박사) ;
  • 신성우 (정회원, 한양대 건축공학과 교수 공학박사)
  • Published : 1997.04.01

Abstract

This study reports the results of flexural test on 6 specimens for maximum reinforcement ratio and 4 specimens for minmum reinforcement ratio with concrete compressive strength 1,000, 1,200 kg/$\textrm{cm}^2$ . The major test variables for the reinforcement ratio designed 0.55$\rho_b$, 0.65$\rho_b$, 0.75$\rho_b$ for maximurm reinforcement ratio test 14/fy $\sqrt[0.72]{\rho}\acute{f}_c$ / $f_y$ for minimum reinforcement ratio test. The test results were compared with ACI 318-95 Code. In the Ultra High Strength Concrete beam, the maximum reinforcement ration should be less than 0.6$\rho_b$ for ductile behavior and the existing minimum reinforcement ratio by ACI Building Code is Sufficiently safe.