Analysis of Instantaneous Voltage Compensator Using 3-Phase PWM Inverter

3상 PWM 인버터를 이용한 순간전압보상기의 해석

  • 최연규 (건국대학교 전기·전자공학부) ;
  • 이승요 (건국대학교 전기·전자공학부) ;
  • 최규하 (건국대학교 전기·전자공학부) ;
  • 목형수 (건국대학교 전기·전자공학부) ;
  • 함형원 (대영전기)
  • Published : 1997.07.01

Abstract

Unbalanced source voltages due to unbalanced loads in the 3-phase power system is decomposed into positive, negative and zero sequence components. Also, assuming there is no neutural path in the system, the zero sequence component is not shown. Therefore, it is possible to compensate unbalanced source voltage by canceling the negative sequency component of the voltages of the source. In this paper, an algorithm compensating unbalanced source voltages by canceling the negative sequence component is presented and analysis of instantaneous voltage compensator using 3-phase PWM inverter is carried out through computer simulation.