폐쇄배전반내 모선의 절연이격거리

A study on the air clearance in the metal-enclosed switchgear

  • 손재현 (한국전기안전공사 전기안전시험연구원) ;
  • 김선구 (한국전기안전공사 전기안전시험연구원)
  • Son, Jae-Hyun (Electrical Safety Laboratory Research Institute Korea Electrical Safety Corporation) ;
  • Kim, Sun-Ku (Electrical Safety Laboratory Research Institute Korea Electrical Safety Corporation)
  • 발행 : 1996.07.22

초록

This paper aims to extract the air clearance in 22.9KV the metal enclosed switchgear. First, we investigated the actual conditions on the clearance in the metal enclosed switchgear which has been used in domestic. The test model and 9 test electrodes for the air insulation strength tests have been designed and manufactured based on the investigation results. To find optimal clearance in the metal enclosed switchgear, we performed 50% flash-over test by the up and down method and lightning impulse withstand voltage test. And we obtained results that the clearance or phase-to-phase is 230 [mm] and clearance or phase-to-earth is 210[mm].

키워드