A Study on the Compensation Method in the Measuring System for Chopped Lightning Impulse

충격전압 재단과 측정을 위한 보상회로에 관한 연구

  • Published : 1996.07.22

Abstract

Lightning impulse voltage is essential to evaluate the insulation performance of electric power apparatus. Recently international standard (IEC-60) on high voltage measurement techniques are being revised. In the draft of this standard, a new calibration method is introduced and the accuracy of most industrial measuring systems is maintained by means of comparison test against the reference measuring systems. Comparison tests of dividers for chopped lightning impulse measurement were rallied out by KERI. The 700kV shielded resisitive divider with and without compensation element were done comparison test with 300kV PTB divider which have the similar charateristics as that were circulated among the laboratories. This paper reports on the calculation results of response charateristics obtained by EMTP and the comparison test results with chopped lightning impulse voltages from 150kV to 250kV. It is demonstrated that KERI are capable of realizing the idea in the revision of the IEC standand, that is, to establish traceability.