345/154kV 초고압 송변전설비 주변에서의 자장의 측정과 분석

Measurement and Analysis of Magnetic Field near 345/154kV UHV Overhead Transmission Lines and Substations

  • 발행 : 1996.07.22

초록

With the three dimensional magnetic field measuring system dealt with in this paper, accurate measurements and analyses of ELF magnetic fields in the vicinity of UHV overhead transmission lines and substations have been conducted. For the field measurements multiturn loop-type sensors have been developed with special consideration of taking lower frequency and spatial components without any distortion. So the measuring system has the frequency bandwidth of 8[Hz] to about 53[kHz] and the response sensitivity of $9.88[mV/{\mu}T]$ in average. A brief description of design rules of the measuring system and measurement procedures is given. The actual surrey near 154 and 345[kV] overhead transmission lines and power subststions was carried out and analyzed. It may be inferred from these results that the maximum magnetic field intensities under typical UHV overhead transmission lines do not exceed $20[{\mu}T]$ so that the field measurements satisfy sufficiently all limits or guidelines that various authorized international institutes recommend.

키워드