Three-Dimensional Electric Field Calculation around the 345kV Sinmasan Substation Busbars

신마산 345kV 전력소 모선하의 3차원 불평등 전계분포 해석

  • Published : 1996.07.22

Abstract

For the rather complicated and time-consuming three-dimensional electric field calculation in the vicinity of substations, this paper proposes a numerical calculation method based on charge simulation method(CSM). In order to represent non-uniform charge distribution on an electrode better, it is subdivided into small segments with linear charge density. Non-uniform arrangement of subdivided segments makes it possible to obtain high accuracy with a small number of variables. As for the arrangement of subdivided segments, effective formulars were derived from multiple regression analysis of many simulations. These formulars make the arrangement of segments fast and effective. The proposed method is applied to the electric field calculation around the 345kV Sinmasan Substation busbars and the distribution of calculated electric fields is compared with that of the measured electric fields.

Keywords