The Diagonosis of Treeing Breakdown Simultaneous Detection on Charge of Partial Discharge and Acoustic Emission Pulse

방전 전하와 음향 방출 펄스의 동시 측정에 의한 트리잉 파괴 진단

  • Choi, J.K. (Dept. of Electrical Eng. KwangWoon univ.) ;
  • Kim, S.H. (Dept. of Electrical Eng. KwangWoon univ.) ;
  • Park, J.J. (Dept. of Electrical Eng. KwangWoon univ.) ;
  • Kim, J.H. (Dept. of Electrical Eng. KwangWoon univ.)
  • 최재관 (광운대학교 전기공학과) ;
  • 김성홍 (광운대학교 전기공학과) ;
  • 박재준 (광운대학교 전기공학과) ;
  • 김재환 (광운대학교 전기공학과)
  • Published : 1996.07.22

Abstract

Recently, the necessity of establishing the way to diagnose the aging of insulation materials and to predict of insulation breakdown become important. The purpose of our work are to investigate the treeing phenomena with a artificial needle shape void by the charge of partial discharge and acoustic emission pulse in each phase angle area at the same time. We have analyzed the ${\Phi}-Q-n$ pattern and the insulation diagnosis of the samples using statistic operators such as charge magnitude and A.E pulse factor, skweness, kurtosis, G,C. Therefore, the relation between the charge of partial discharge and A.E pulse will be helpful and efficient to predict the breakdown just before the breakdown occure.

Keywords