Proceedings of the KIEE Conference (대한전기학회:학술대회논문집)
- 1996.07b
- /
- Pages.853-855
- /
- 1996
The On-Line Measuring of Dissipation Factor on pole Transformer
주상 변압기의 절연유 유전정접 활선 측정 기법
- Lee, Su-Kil (Dept. of Electrical Engineering in Soong Sil Univ.) ;
- Kim, Jae-Chul (Dept. of Electrical Engineering in Soong Sil Univ.) ;
- Yoon, Yong-Han (Dept. of Electrical Engineering in Soong Sil Univ.) ;
- Lee, Bo-Hoo (Dept. of Electrical Engineering in Soong Sil Univ.) ;
- Kim, Oun-Seok (KERI)
- 이수길 (숭실 대학교 전기 공학과) ;
- 김재철 (숭실 대학교 전기 공학과) ;
- 윤용한 (숭실 대학교 전기 공학과) ;
- 이보호 (숭실 대학교 전기 공학과) ;
- 김언석 (한국 전기 연구소)
- Published : 1996.07.22
Abstract
This paper describes the dissipation factor measuring techniques of insulating oil on the operating transformer by using digital signal processing. After applying voltage to the electrodes which is installed In a transformer, acquiring source voltage and current of electrodes and using cross-correlation techniques. we can check the dissipation factor of insulating oil. To Improve measuring accuracy and the speed of process, we use hardware such as TMS320C31 DSP board and analog filter and software such as cross-correlation techniques, rectangular window, and digital filtering techniques. We simulated the measuring accuracy and the degree of the noise effect of this new measuring techniques by using computer simulation, and compared the simplified measuring devices with schering bridge on degraded insulating oil. The result showed that this measuring technique can be used as diagnostic method on the pole transformers.