Determination Method of O.T. Aging Level by Model Partial Discharge Test

모의 부분방전 시험에 의한 O.T. 절연열화 판정기준 설정 방안

  • Published : 1995.10.01

Abstract

This paper describes a diagnosis of transformer by ultrasonic signal due to partial discharge. The ultrasonic signal can be measured when partial discharge is generated in a real transformer. The trend of partial discharge in transformer was estimated by counting the number of ultrasonic signals until insulation paper in the point-to-plane electrode is destroyed. The number of ultrasonic signals is closely related to the number of the electrical signals by partial discharge. The trend of the ultrasonic signal number could easily be distinguished by taking moving average.

Keywords