화력 발전기 고정자 권선에서의 수소 압력에 따른 부분 방전 특성

The Effect of Hydrogen Pressure on Partial Discharge Spectroscopy in Turbine Generator Winding Insulations

  • 발행 : 1995.07.20

초록

For hydrogen-cooled large turbine generators, partial discharges in ground wall insulations are suppressed by high hydrogen pressure. The first goal of the experiment is to investigate the effect of hydrogen pressure on partial discharge activity and aging rate in turbine generator winding insulations. A series of tests have been performed on two groups of the accelerated aging experiments. The first group of stator windings was aged under hydrogen pressure of 4 atm while the second group of stator windings was aged under air atmosphere. The stator windings aged under air atmosphere suffer from larger partial discharge magnitude with larger voids at high electrical stress than those under hydrogen pressure. The second goal of the experiment is to evaluate the validity of on-line measurement technique which is normally measured under hydrogen environment. The test results show that further experiments are needed to apply the on-line scheme to turbine generator being under high hydrogen pressure.

키워드