Modeling and prediction of rapid pollution of insulators in substations based on weather information

  • 발행 : 1994.10.01

초록

Mathematical model of the pollution rate of substation insulators is constructed, taking the model parameters as wind speed, wind direction, typhoon conditions and rainfall in an hourly basis. The main feature of model construction is to distinguish the effect of each parameter by separately analyzing the positive and negative pollution causing factors. Model parameters for the insulators of Karatsu substation, Saga, Japan were estimated and model validation was done using the actual data, in which the pollution deposits on the insulators were measured using pilot insulator and 'salt meter'. The proposed model of the pollution rate [mg/cm$^{2}$/hr] enables the identification of the effective parameters and prediction of the pollution rate so that it helps for the automatic decision making for insulator cleaning or the model can be used as a tool for the substation engineers to make precautionary measures.

키워드