신경망을 이용한 전력용 변압기의 부분방전 위치추정

Estimation of The Partial Discharge Position Using Neural Networks in The Power Transformers

  • Kim, Jae-Chul (Dept. of Electrical Engineering, Soongsil University) ;
  • Yoon, Yong-Han (Dept. of Electrical Engineering, Soongsil University) ;
  • Kim, Young-Sik (Dept. of Electrical Engineering, Soongsil University) ;
  • Kweon, Dong-Jin (Dept. of Electrical Engineering, Soongsil University)
  • 발행 : 1994.07.21

초록

This paper presents a new method for estimating partial discharge position using improved cross-correlation technique and neural networks in the power transformer. When ultrasonic signal is occurred by partial discharge, we detected these signals and calculated cross-correlation values with Hamming window. Also, we estimated partial discharge position using neural network with cross-correlation values. In the result of case study, we can estimate more accurately the partial discharge position than any other algorithms.

키워드