GIS내에서 금속이물이 절연파괴에 미치는 영향

The Effect of Conducting Particles on Breakdown Phenomena in GIS

  • 발행 : 1994.07.21

초록

$SF_6$ gas has become an important insulation medium in modern electric power apparatus, because of its high insulation withstand levels and good arc quenching capability. For the application of $SF_6$ gas in GIS the estimation of insulation properties is a fundamental point. Moreover the reduction of withstand levels in case of inhomogeneous fields caused by particles or fixed protrusions is of special interest. It is known that the presence of free conducting particles in GIS can significantly lower the insulating level of $SF_6$ gas at elevated pressure and also it has been recently shown that dielectric strength is greatly reduced by fast transients such as disconnector surges where metallic particles are involved. In this paper, we have disigned the particle test chamber rated 362kV for the purpose of investigating the discharge characteristics in SF6 gas where inhomogenius fields are caused by metallic particles.

키워드