Load Center Concept Equivalent by T/L Loss Identification

부하 중심점 개념의 전력 시스템 정태 등가 축약

  • Baek, Soo-Youl (Hong-Ik University, Dept. of Electrical & Control Engr.) ;
  • Kim, Jung-Hun (Hong-Ik University, Dept. of Electrical & Control Engr.) ;
  • Shim, Keon-Bo (Hong-Ik University, Dept. of Electrical & Control Engr.) ;
  • Lee, Bong-Yong (Hong-Ik University, Dept. of Electrical & Control Engr.)
  • 백수열 (홍익대학교 공과대학 전기.제어 공학과) ;
  • 김정훈 (홍익대학교 공과대학 전기.제어 공학과) ;
  • 심건보 (홍익대학교 공과대학 전기.제어 공학과) ;
  • 이봉용 (홍익대학교 공과대학 전기.제어 공학과)
  • Published : 1992.07.23

Abstract

A simple and practial equivalent technique has been presented in this study. Arbitrary number of bus system can be aggregated to the equivalent one-bus system, equivalents are totel real, and reactive bus powers and T/L losses viewing form boundary buses. Variables to be determined are line impedance between boundary buses and the equivalent bus, voltage and angle of that bus. IEEE 14 bus system is used to demonstrate the proposed method. even in contingency cases very good results have been obtained

Keywords