A Study on the fast-rising switching surges charateristics in the 154KV transformers

154KV 변압기의 계통개폐 급준파 전압특성 연구

  • Published : 1992.07.23

Abstract

This paper deals with the mesurement and the analysis by means of EMTP simulation for the fast-rising switching surges. The fast-rising surges having up to 180ns of front time and 3.42 p.u of peak value were measured at the 154KV substations. The fast-rising surges are expected to cause electric breakdown because the penetrating surges to the transformers result in the higher stress in the winding end than the average stress along the winding.

Keywords