대한전기학회:학술대회논문집 (Proceedings of the KIEE Conference)
- 대한전기학회 1992년도 하계학술대회 논문집 B
- /
- Pages.775-778
- /
- 1992
고낙차 조건에서의 154kV XLPE CABLE 설치
An Installation of 154kV XLPE CABLE in Steep Slope Condition
- Hwang, Soon-Chul (GoldStar Cable CO., Ltd.) ;
- Lee, Chang-Su (GoldStar Cable CO., Ltd.) ;
- Lee, Cheon-Ku (GoldStar Cable CO., Ltd.) ;
- Goh, Chang-Sung (GoldStar Cable CO., Ltd.)
- 발행 : 1992.07.23
초록
In 1980, 154kV OF cable was installed at the Cheong-Pyeong pumped-storage power station. Effective head of this pumped-storage station is 250m between upper and lower re-servior and length of cable route is 750m. However, several failures have happened owing to steep slope during the operation. 154 kV XLPE cable was applied for this power station to eliminate a lack of stability on account of steep slope and successfully installed in 1991. Meanwhile, installation procedure brings about many problem to be solved. In this paper, we describe the counter measure of cable sliding phenomena caused by heat shrinkage as well as the method of installation of cable under the steep slope condition. And hereafter, we think this paper will be a good reference to design and installation of 154kV XLPE cables in steep slope turnnel at urban areas.
키워드