열화된 XLPE 케이블의 열지급전류

Thermally Stimulated Currents in Aged XLPE Cable Insulation

  • 김상준 (한전기술연구원 배전연구실) ;
  • 이남우 (한전기술연구원 배전연구실) ;
  • 정동원 (한전기술연구원 배전연구실) ;
  • 고인석 (한전기술연구원 배전연구실)
  • 발행 : 1991.07.18

초록

In order to evaluate degradation of the aged power cables, thin slices(200m) cut from the aged cables were prepared for thermally stimulated current measurements. Throughout the temperature range, 140 to $280^{\circ}C$ the TSC is greater for the aged material, and sharp peak is observed at $158^{\circ}C$ and $210^{\circ}C$.