대한전기학회:학술대회논문집 (Proceedings of the KIEE Conference)
- 대한전기학회 1990년도 하계학술대회 논문집
- /
- Pages.279-282
- /
- 1990
로고스키 코일과 초음파 센서를 이용한 변압기내 부분방전 탐지 및 위치검출
Detection and Location of Partial discharge in Transformers Using Logoski coil and Ultrasonic sensor
- Kwak, Hee-Ro (Soong Sil UNIV.) ;
- Kim, Jae-chul (Soong Sil UNIV.) ;
- Kim, Eung-Sang (Soong Sil UNIV.) ;
- Han, Min-Koo (Seoul Nat.UNIV.) ;
- Kwan, Tae-Won (Research Center KEPCO) ;
- Yoon, Young-Beum (Research Center KEPCO)
- 발행 : 1990.07.05
초록
This paper describes an nstrument for the detection and geometric location of partial discharge(PD) sources in transformers. This instrument measures electric current pulses and ultrasonic pulses simultaneously, counts the number of electrical pulse and determines the geometric location of PD in transformers. It was found that there is a relationship between partial discharge magnitude and pulse repetition rate when the applied test voltage and oil temperature were varied. Through the laboratory test using model transformer, it was clarified that this detector could be used, satisfactory for detecting and locating of PD in the transformer.
키워드