A new method for measuring the degradation level of transformer insulating oil in use

변압기 절연유의 열화 검출에 관한 연구

  • Published : 1988.11.25

Abstract

Aging process in transformer insulating oil is studied by measuring the leakage current in ceramic sensor. the current of a sensor developed if this paper shows a close relationship with the acid value and the breakdown voltage of the transformer oil. The sensor has excellent physico-chemical reaction to the oil and stable adsorption of conductive impurities. Therefore the experimental data show good reproducibility. From the detailed analysis of the leakage current, it may be proposed that the condition of transformer insulating oil in service can be checked portably.

Keywords