765 KV 2 회선(回線) 송전선(送電線) 절연협조(絶緣協助)

Insulation coordination of 765 KV double circuit transmission line

  • 발행 : 1988.07.01

초록

This paper covers the insulation coordination of 765 KV transmission line in Korea Electric Power Corporation. The design for the lightning, switching surge, and contamination was conducted to increase the reliability of 765 KV line. The authors have used the result of a limited Westinghouse ANACOM swiching surge study of the Korea Electric Corporation's 765 KV Expansion plan. The study investigated the switching surge overvoltage distribution and maximum switching overvoltage when relosing 765 KV lines. They used the technical data of the suspension insulator for the contamination design, which was available from a foreign insulator manufacture. From this paper, the authors find out that the contamination design dominates to determine the number of insulator and the SOV design dominates the air clearance in the tower. Afterwards the authors will confirm this design by Demonstration Test with Korea Electro-technology Research Institute.

키워드