Dynamic Analysis of Diesel Generators on Starting Large Induction Motors

대용량유도전동기 기동시의 비상용 디젤발전기 동특성 해석

  • 한풍 (한국전력기술주식회사) ;
  • 조성돈 (한국전력기술주식회사)
  • Published : 1987.11.20

Abstract

It is important to evaluate the voltage characteristics of diesel generator as an emergency power supply in nuclear power plant. On loss of offsite power sources, emergency safeguard loads required to safely shutdown the reactor should be supplied by diesel generator. This paper presents the dynamic stability program to evaluate diesel generator performance as an emergency power system. The results Indicate the diesel generator ability to start the motors successfully seems to life in its impedances and inertias.

Keywords